top of page
MIC-2501  Insulation Resistance Meter
MIC-2501 insulation resistance meter
Insulation resistance measurement:
Key Features:
  • Continuity measurement of protective and equipotential conductors according to EN 61557-4

  • with the >200 mA current.

  • Leakage current measurement.

  • Measurement of alternating and direct voltages in the 0...750 V range.

  • Built-in rechargeable battery pack.

  • The instruments meet the requirements of the EN 61557 standard.

  • The ability to charge from car lighter (12 V) socket (additional accessories).

Specifications:

Electrical Safety:

type of insulation                                        double, in acc. with EN 61010-1 and IEC 61557

measurement category                                      in acc. to IV 600 V (III 1000 V) EN 61010-1

case protection rating in acc. with EN 60529                                                                 Ip65

Other technical specifications:

power supply of the meter ...........  NiMH 9.6 V - 2 Ah battery pack and power supply 12 V

weight of the meter ......................................................................................... approx.0.9kg

dimensions .............................................................................................200 x 180 x 77 mm

display ............................................................................................... LCD segment display

measurement results ...................................................... memory 990 cells, 11880 records

transmission of measurement results .......................................................................... USB

humidity .............................................................................................................. 20%...90%

*For full Technical Specifications, please refer to PDF Data Sheet

- selectable measurement voltage in the 100…2500 V range with

  100 V step,

- continuous indication of insulation resistance or leakage current,

- automatic discharge of capacitance of tested object after the

  insulation resistance measurement,

- acoustic signalling of five-second periods to facilitate obtaining time

  characteristics,

- measured test times T1, T2 i T3 to measure one or two absorption

  coefficients in 15, 60 and 600 s,

- indication of actual test voltage during the measurement,

- protection against measuring live objects,

- two and three-lead measurement method,

Standard Accessories:
  • "crocodile" clip 5,5 kV; black

  • "crocodile" clip 5,5 kV; red

  • "crocodile" clip 5,5 kV; blur

  • pin probe 5 kV with banana connector; red

  • pin probe 5 kV with banana connector; black

  • test lead banana plug; 1,8 m; 5 kV; red

  • test lead banana plug; 1,8 m; 5 kV; blue

  • test lead banana plug; 1,8 m; 5 kV; black

  • USB cable

  • carrying case

  • power supply adaptor Z7

  • meter harness

  • DVD with software, including “SONEL Reader” (reading data from memory)

  • calibration certificate

  • warranty card

bottom of page