top of page
BDV.100KVT Transformer Oil BDV Tester
About the BDV.100KVT:

Used for power networks, railway systems, large-scale petrochemical plants, etc.

Electrical equipment that rely on oil-filled insulation require testing of the insulating oil dielectric strength as a common and standard practice.

To meet market needs, we have developed and produced a series of insulating oil dielectric strength testers according to:

  • National standard GB/T507-2002

  • Industry standard DL429.9-91

  • Latest Electric Power Industry Standard DL/T846.7-2004

  • IEC60156-1995 compliant

A single-chip microcomputer as the core provides a fully automated, high-accuracy instrument.

Standard Accessories
  • Main Instrument (1)

  • Glass Test Vessel 400ml (1)

  • Mushroom Electrode Set (1)

  • Elbows (2)

  • Magnetic Stirrers (2)

  • Gap Indicators 1, 2 & 2.5mm Set (1)

  • Magnet Stirrer Retriever (1)

  • Power Cord (1)

  • Fuses (2)

  • Print Paper (2)

Specifications:

Output voltage

  • 0~100KV rms

Voltage distortion rate

  • ±1%

Booster capacity

  • 1.5KVA

Measuring accuracy

  • ±1%

Flashover twitch time

  • <10µs

Supply voltage

  • AC220V±10% 50Hz±1 Hz

Power consumption

  • 300W

Applicable temperature

  • 0℃~55℃

Weight

  • 28kg

Overall dimension

  • 460×280×320mm

  • With the microprocessor, the instrument automatically completes the withstand voltage test for oil circulation with a range of 0 ~ 100KV (including boosting, maintaining, mixing, standing, printing, and data export)

  • Wide temperature sample range 0 - 99⁰C

  • Large LCD display with touch screen operation

  • User-friendly operation. The instrument will automatically complete the withstand voltage test on one sample

  • Breakdown voltage value of 1 to 9 times and will be automatically saved

  • After the test, the thermal printer will print each breakdown voltage value and average value

  • Power-down data preservation

  • The instrument can save 100 tested results

  • The voltage is accurate at 50Hz

  • Equipped with over-voltage, over-current protection to safeguard the operators

  • Displays time & date on test results

  • Communication includes RS232 & USB interface for exporting test data

bottom of page