top of page
MRU-200 GPS  Earth Resistance Meter
MRU-200 GPS
Key Features:

MRU-200-GPS is the unique meter in the market which uses all measurement methods.

  • measurement of resistance of auxiliary electrodes R and R , S H

  • measurement of interference voltage,

  • measurement of interference frequency,

  • measurement in the presence of interference voltage in the power network with frequency 16 2/3 Hz, 50Hz, 60Hz and 400Hz (with automatic selection of proper frequency of measuring signal or with manual selection),

 

  • selection of maximum measuring voltage (25V and 50V)

  • introducing the distance between the electrodes for the resistivity

       in metres (m) and feet (ft),

  • memory of 990 measurements (10 banks of 99 cells each),

  • calibration of clamp used,

  • real time clock (RTC),

  • data transmission to the computer (USB),

  • indication of battery state.

Measurement of earth ground impedance:

- with the use of the impulse method (without the necessity for

  disconnecting the measured earthing systems),

- three types of the measurement impulse (4/10μs; 8/20μs;

  10/350μs)

Measurements of protective connection and equipotential
bonding continuity:

- with auto-zero function - with current ≥ 200 mA - in accordance with

  EN 61557-4.

Specifications:
Measurements of earth ground resistance:

- with the use of auxiliary probes (three and four-lead methods),

- with the use of auxiliary probes and clamp (for measurements of

  multiple earthing, three-lead + clamp),

- with the use of double clamps (for earthing measurements, when

  the use of auxiliary probes is not possible),

- resistance of auxiliary probes R and R , S H

- voltage and frequency of the interfering signal,

- in the presence of interfering voltages in power systems with the

  frequency of 16⅔ Hz, 50 Hz, 60 Hz and 400 Hz (with the automatic

  or manual selection of proper measurement signal frequency),

- selection of maximal measurement voltage (25 V or 50 V),

- calibration of clamp used.

Electrical safety

- type of insulation:                     double, according to EN 61010-1and IEC 61557, EMC

- measurement category:                                             CAT IV 300V acc. to EN 61010-1

- protection class acc. to EN 60529                                                                          IP54

Rated operational conditions:

- operation temperature................................................................................ -10...+50°C

- storage temperature................................................................................... -20...+70°C

- humidity.......................................................................................................... 20...80%

Other technical data:

- LCD display.................................................................................. graphic, backlighted

- interface................................................................................................................ USB

- number of measurements carried out of set of batteries................................... > 1200

- warranty....................................................................................................... 36 months

.*For full Technical Specifications, please refer to PDF Data Sheet

Measurements of soil resistivity (with Wenner method):

- input of probes spacing distances in metres (m) or in feet (ft).

Standard Accessories for the MRU-200 GPS:
Optional Accessories:

- Test lead with banana plug; 1,2m; red

- Test lead with banana plugs 2,2m; black

- Test lead on a reel with banana plugs; 25m red

- Test lead on a reel with banana plugs; 25m blue

- Shielded test lead on a reel with banana plugs; 50m yellow

- USB transmission cable

- charger for battery loading from the socket of car lighter (12V)

- Earth contact test probe (rod); 0,30m - (4 pcs.)

- Carrying case L2

- Ni-MH battery package 4,8V 4,2Ah

- Crocodile clip K01; black

- Crocodile clip K02; red

- Cramp

- Power supply adaptor Z7

- Cable for battery charger

- Hanging straps

- Calibration certificate issued by calibration laboratory

- Hard carrying case

- Earth contact test probe (rod); 0,80m

- Test lead with banana plugs 2m (N-1)

- Current clamp C-3 (Ø=52mm)

- Current clamp N-1 (Ø=52mm)

- Current flexible clamp (Rogowsky coil) F-1 (Ø=400mm)

- Battery case LR14 (size C)

- Carrying case L3

- Software for creation of documentation from

  electrical measurements „SONEL PE4”

 

bottom of page