top of page
MPI-530-IT  Multifunction Electrical Installation Meter
MPI-530-IT

Bluetooth Mini Keyboard (optional)

Measurement of short-circuit loop impedance:

- impedance measurement with resolution 0.001 and 23 A current

  (44 A phase-to-phase)

- short-circuit resistor R =10 ZW

- measurement range: 95...440 V, frequency 45...65 Hz,

- measurement of short circuit loop impedance with resolution 0.01 ,

  in protected systems without tripping the RCD’s with I ≥ 30 mA Δn

- automatic calculation of short-circuit current, differentiating

  between phase-to-phase and phase-to-neutral voltage,

- measurements using UNI-Schuko plug with measurement

  triggering button (also when L and N leads are exchangeable) or 

  1.2 m, 5 m, 10 m, 20 m test leads, with optional use of 3-phase

  socket adapters (AGT),

- selection of installation protections and automatic evaluation of

  measurements results

Examination of AC, A and B type residual current devices::

- MPI-530-IT allows measurements in IT network,

- measurement of general, short-time delay and selective RCDs of

  rated residual current 10, 30, 100, 300, 500 and 1000 mA,

- a function of automatic measurement of the full set of RCD 

  parameters (after a single push of the "START" button, the meter

  performs the entire defined cycle of measurements, including the

  L-PE short-circuit loop impedance measurement with 15 mA

  current),

- the shape of leakage current characteristics selected by the user:

  sinusoidal (starting with the rising or falling edge), pulsating

  unidirectional current (positive or negative), pulsating unidirectional

  current with 6mA direct current offset (positive or negative),

  direct current (positive or negative),

- measurement of the I operating current with rising current, A

- measurement of the t tripping time for I , I , 2I , 5I , A Δn Δn Δn Δn

- measurement of the U touch voltage and the R protective

  conductor resistance B E without tripping the RCD,

- detection of swapped L and N conductors in a socket; no influence

  on the performance of measurements,

- capability of the I tripping current and the t actual tripping time

  measurement A AI with just one RCD tripping,

- voltage measurements in the range of 95...270 V.

Insulation resistance measurement:

- test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V,

- insulation resistance measurements up to 10 G ,

- capability of in-socket measurement with the use of the UN

  Schuko adapter,

- acoustic signalling of 5-second time intervals to facilitate capturing

  time characteristics,

- protection of the meter against the presence of voltage on the

  object and the appearance of voltage during measurement,

- automatic discharge of capacitance of the object after finishing the

  measurement,

- automatic measurement of all resistance combinations of 3, 4 and

  5-core cords with the use of the additional AutoISO-1000C 

  adapter.

Measurements of earth resistance and earth resistivity:

- measurement with 3- or 4-lead technical method and 2 auxiliary

  electrodes,

- measurement with the 3-pole method with and additional clamp,

- measurement with 2-clamp method,

- measurement of earth resistivity - range of measurement: 0.0 Ωm

  ...9.99 kΩm, input of rods spacing distances in meters (1...30 m) 

  or in feet (1...90 ft)

Key Features:
  • Measurement and recording of voltage, frequency, AC, cosφ and power

      (active, reactive and apparent), voltage and current harmonics up to 40, 

      THD.

  • Quick verification of correctness of the PE conductor connection with the use of a touch electrode.

  • Phase sequence checking.

  • Innovative memory with description of measurement points, facilities,

       names of customers (max. 10000 results of each measurement).

  • Power supply from rechargeable of disposable batteries (optional).

Low-voltage measurement of protective connection
and equipotential bonding resistance:

- measurement of the protective conductor continuity with current 200 mA

  in both directions (in accordance with the EN 61557-4 standard),

- low-current measurement of resistance with acoustic and light signalling,

- automatic calibration of test leads - capability of using test leads of any  

  length.

Specifications:

Electrical safety

- type of insulation:                     double, according to EN 61010-1and IEC 61557, EMC

- measurement category:                                                    IV 300 V acc. to EN 61010-1

- protection class acc. to EN 60529:                                                                         IP54

Other technical specifications

- power supply:.................... Ni-MH rechargeable or LR14 alkaline disposable batteries

                                                                                                             (4 pcs.) (optional)

.*For full Technical Specifications, please refer to PDF Data Sheet

Illuminance measurements:

- range of measurement: 0.1 lx...19.9 klx,

- measurement in lux (lx) or foot-candle (fc),

- measurement using external photo

   detector (optional)

Standard Accessories for the MPI-530-IT & MPI-530:
Optional Accessories for the MPI-530-IT:

- Adapter with START button with UNI-Schuko (WS-03)

- Test lead with banana plug; 1,2m; yellow

- Test lead with banana plug; 1,2m; blue

- Test lead with banana plug; 1,2m; red

- Test lead on a reel with banana plugs; 15m; blue

- Test lead on a reel with banana plugs; 30m; red

- USB cable

- Pin probe with banana connector; yellow

- Pin probe with banana connector; red

- Pin probe with banana connector; blue

- "Crocodile" clip K02; yellow

- "Crocodile" clip K02; red

- Earth contact test probe (rod); 0,30m (2 pcs)

- Bluetooth mini-keyboard

- Carrying case L2

- Set of hanging straps

- NiMH rechargeable battery

- Lead for battery loading from the socked of car lighter (12V)

- Cable for battery charger

- Power supply adapter Z7

- Sonel Reader software

- Calibration certificate

- Adapter WS-04 with UNI-Schuko

- Adapter AutoISO 1000C

- Test lead on a reel with banana plugs; 50m;

- Test lead on a reel with banana plugs; 25m; blue

- Test lead with banana plug 5m; red

- Test lead with banana plugs; 10m; red

- Test lead with banana plug 20m; red

- Current clamp C 3

- Current clamp

- Transmitting clamp N1 (with test lead)

- Flexible clamp F-1 Ć 40cm

- Flexible clamp F-2 Ć 25cm

- Flexible clamp F-3 Ć 13cm

- Triple phase socket adapter AGT-16P

- Triple phase socket adapter AGT-32P

- Triple phase socket adapter AGT-63P

- Triple phase socket adapter AGT-16C

- Triple phase socket adapter AGT-32C

- Adapter for industrial sockets AGT-16T

- Adapter for industrial sockets AGT-32T

- Light meter probe LP1 with WS-06 plug

- Box for batteries

- Mini bluetooth keyboard with casing

- RCD breaker testing adapter TWR-1J

- Earth contact test probe (rod); 0,80m

- Software for creation of documentation

  from electrical measurements "Sonel Reports"

- Software „SONEL Schematic”

- Hardware Adapter for Sonel PE program

 

bottom of page