MIC-5010 & MIC-5005 Insulation Resistance Meters
Key Features:
-
Digital filters function for measurements in high noise environment
(10 s, 30 s, 60 s).
-
MIC-5010: Continuity measurement of protective connections and equipotential bonding in accordance with
-
EN 61557-4 with current > 200 mA.
-
MIC-5010: Adjustable limits for measured resistance R and R . ISO CONT
-
Measurement of leakage current during insulation resistance testing.
-
Measurement of capacitance during the measurement of R . ISO
-
DC and AC voltage measurement in the range of 0…600 V.
-
990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR
-
adapter) or through a USB cable.
-
Power supply from main power line or battery packs, low battery warning indicator, built-in fast charger.
-
Keyboard and display backlit (MIC-5005 - only display).
-
The instruments meet the requirements of the EN 61557 standard.
Insulation resistance measurement:
- measurement voltage any in the range of 50…1000 V at 10 V and
1000...5000 V at 25 V resolution,
- continuous indication of measured insulation resistance or leakage
current,
- automatic discharge of measured object capacitance voltage after
the end of insulation resistance measurement,
- acoustic signaling of 5 seconds intervals to facilitate capturing time
characteristics,
- metered T , T and T test times for measuring one or two absorption
coefficients from the range of 1…600 s, 1 2 3
- adjustable measuring time to 99'59'’,
- polarization index (PI) and dielectric absorption ratio (DAR)
measurement,
- indication of actual test voltage during measurement,
- 1.2 mA and 3 mA test current,
- step voltage insulation resistance measurement (SV),
- Dielectric Discharge calculation (DD),
- protection against measuring live objects,
- measurements with test leads up to 20 m
Specifications:
Electrical Safety:
type of insulation double, in acc. with EN 61010-1 and IEC 61557
measurement category in acc. with IV 600 V (III 1000 V) EN 61010-1
case protection rating in acc. with EN 60529 IP54 (IP67 - with lid closed)
Other technical specifications:
power supply of the meter .....................................................................built-in battery pack
weight of the meter ............................................................................................approx. 7kg
dimensions............................................................................................390 x 310 x 170 mm
display ................................................................................................ LCD segment display
measurement results memory ................................... 990 cells of memory (11880 records)
transmission of measurement results ......................................... USB or wireless interface
*For full Technical Specifications, please refer to PDF Data Sheet
Standard Accessories:
-
"crocodile" clip 5,5 kV; black
-
"crocodile" clip 5,5 kV; red
-
"crocodile" clip 5,5 kV; blue
-
pin probe 5,5 kV with banana connector; red
-
pin probe 5,5 kV with banana connector; black
-
power cord
-
battery pack (built-in)
-
test lead banana plug; 1,8 m; 10kV; red
-
test lead banana plug; 1,8 m; 10 kV; blue
-
test lead banana plug; 1,8 m; 10 kV; black; shielded
-
USB cable
-
carrying case L4 for accessories
-
“SONEL Reader” software
-
calibration certificate