Insulation resistance measurement:
Key Features:
-
Measurement of leakage current during insulation resistance testing.
-
Measurement of capacity during the measurement of R . ISO
-
Continuous measurement of surrounding temperature with the capability of recording results in memory.
-
DC and AC voltage measurement in the range of 0…600 V.
-
990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR-1
-
adapter) or through a USB cable.
-
Power supply from battery packs.
-
The instruments meet the requirements of the PN-EN 61557 standard.
Specifications:
Electrical Safety:
type of insulation double, in acc. with EN 61010-1 and IEC 61557
measurement category in acc. to IV 600 V (III 1000 V) EN 61010-1
case protection rating in acc. with EN 60529 Ip54
Other technical specifications:
power supply of the meter ......................................... SONEL L-1 NiMH 9.6V battery pack
weight of the meter ......................................................................................... approx.1.3kg
dimensions............................................................................................. 260 x 190 x 60 mm
display ............................................................................................... LCD segment display
measurement results ...................................................... memory 990 cells, 11880 records
transmission of measurement results .......................................... USB o Wireless interface
humidity ............................................................................................................. 20%...90%
*For full Technical Specifications, please refer to PDF Data Sheet
- selectable measurement voltage 100, 250, 500, 1000 V or any in
the range of 50…2500 V at 10 V resolution,
- continuous indication of measured insulation resistance or leakage
current,
- automatic discharge of measured object capacitive voltage after
the completion of insulation resistance measurement,
- acoustic signaling of 5 seconds intervals to facilitate capturing time
characteristics,
- metered T , T and T test times for measuring one or two absorption
coefficients from the range of 1…600 s, 1 2 3
- capability of automatic measurement of multi-wire cables with the
additional AutoISO-2500 adapter,
- indication of actual test voltage during measurement,
- protection against measuring live objects.
Continuity measurement of protective connections and equipotential bonding in accordance with PN-EN 61557-4
with current > 200 mA.
Circuit continuity and resistance measurement at low voltage.
- circuit resistance measurement ( < 999 Ω) with current < 15 mA,
- quick acoustic signaling for a circuit of resistance lower than 10 Ω
- compensation (automatic zero) of test lead resistance.
Standard Accessories:
-
test lead banana plug; 1,8m; 5kV; red
-
test lead banana plug; 1,8m; 5kV; blue
-
test lead banana plug; 1,8m; 5kV; black
-
USB cable
-
"crocodile" clip K02 5kV; black
-
"crocodile" clip K05 5kV; red
-
"crocodile" clip K05 5kV; blue
-
pin probe 5kV with banana connector; red
-
pin probe 5kV with banana connector; black
-
USB cable
-
carrying case
-
power supply adaptor Z7
-
meter harness
-
DVD with software, including “SONEL Reader” (reading data from memory)
-
calibration certificate
-