MIC-2 Insulation Resistance Meter
Insulation resistance measurement:
- selectable test voltage 250 V or 500 V,
- continuous indication of the measured insulation resistance value,
- automatic discharge of capacitance of the measured object after
finishing the insulation resistance measurement,
- acoustic signalling of 5-second time intervals to facilitate capturing
time characteristics,
- protection against measurements of energised objects.
Low-voltage measurement of resistance within
the range of 0...2000Ω:
- measurement with current < 10 mA and the resolution of 0,1Ω,
- quick acoustic signalling for the circuit of resistance smaller than
10Ω.
Key Features:
-
In the event of voltage detection on the object during insulation resistance measurement or low-voltage resistance measurement, MIC-2 meter automatically switches to the voltage measurement mode.
-
Measurement of direct and alternating voltages within range of 0...600 V:- automatic detection of voltage type (direct/alternating).
-
Automatic selection of measurement ranges.
-
LCD and keyboard backlit.
-
Automatic power-off of an unused instrument (AUTO-OFF).
Specifications:
Electrical Safety:
- type of insulation double, in acc. with EN 61010-1 and IEC 61557
- measurement category CAT IV 600 V (III 1000 V) acc. to EN 61010-1
- enclosure protection rating acc. to EN 60529 ......................................................... IP65
Other technical specifications:
- power supply of the meter...............................................2 LR03 batteries (size AAA) or
2 AAA rechargeable batteries
- dimensions..............................................................................approx. 240 x 60 x 30 mm
- weight of the meter....................................................................................approx. 0.3 kg
- R measurement current .................................................................1.2 mA ± 0.2 mA ISO
- max. interference voltage, at which the R measurement is performed ............ 20 V ISO
- number of R measurements (alkaine batteries).............................................. > 500 ISO
- auto-off timeout.................................................................................................5 minutes
- electromagnetic compatibility....................................compliance with the EN 61000-6-3
and EN 61000-6-2 standards
Nominal operating conditions:
- operating temperature .....................................................................................0...+40°C
- reference temperature.......................................................................................23 ± 2°C
- storage temperature.......................................................................................20...+70°C
*For full Technical Specifications, please refer to PDF Data Sheet
Standard Accessories:
Optional Accessories:
- AGT-16P (triple phase socket adapter)
- AGT-32P (triple phase socket adapter)
- AGT-63P (triple phase socket adapter)
- Carry case S2
- Calibration certificate
- "Crocodile" clip K01; black
- Pin probe with banana connector, black
- Calibration certificate
- Batteries