WR.40S Three Phase Transformer Winding Resistance Tester
About the WR.40S:
-
DC winding resistance tester is designed to measure DC resistance of inductive devices, such as transformers and power inductors.
-
The instrument is compact in size and has a high level of accuracy with fast measurement cycle.
-
WR.20S is ideal for measuring transformer windings and DC resistance of large power inductance equipment.
-
Polyphase winding resistance and de-magnetization function.
-
Suitable for Transformers up to 7MVA / 35kV models.
Specifications:
Current
-
Single phase: 1A, 5A, 10A, 20A, 40A
-
Three phase: 1A, 5A, 10A, 20A
Range
-
Single phase:
-
1A: 10mΩ~20Ω
-
5A: 1mΩ~4Ω
-
10A: 1mΩ~2Ω
-
20A: 1mΩ~1Ω
-
40A: 1mΩ~0.5Ω
-
-
Three phase:
-
1A: 10mΩ~6Ω (per phase)
-
5A: 1mΩ~1Ω (per phase)
-
10A: 1mΩ~0.6Ω (per phase)
-
20A: 1mΩ~0.3Ω (per phase)
-
Accuracy
-
±0.2% (full range)
Max Resolution
-
0.1μΩ
Data Saving Capacity
-
200 groups
Power
-
AC 220V±22V, 50Hz±2Hz
Working Environment
-
Temperature: 0-40℃
-
Relative humidity: ≤80%
Dimensions
-
428mm × 350mm × 230mm
Weight
-
13.4kg