VLF80/90kV

Introduction to the VLF.Series:
-
The VLF sine wave test series is a compact, robust, and portable VLF sine wave test system designed for medium and high-voltage cables.
-
Featuring air cooling, this system can operate continuously, making it ideal for testing with 0.1 Hz sine wave voltages.
-
The VLF testing system is user-friendly, with single-button operation, a simple menu structure, and a large LCD display for easy control.
-
This series of ultra-low frequency AC withstand voltage testers is perfect for on-site testing of insulation and voltage withstand capacity in polyethylene, crosslinked polyethylene cables, and other high-voltage electrical equipment used by power departments and industrial sectors.
-
Unlike DC voltage withstand tests, this device is considered non-destructive and serves as a great alternative to AC frequency voltage withstand testing.
-
The Model S units also offer a DC withstand test function.
Specs
VLF80/90kV
-
Rated Voltage: 80/90kV (Peak)
-
Load Carrying Capacity:
-
≦10µF (within 50kV)
-
≦4µF (above 50kV)
-
-
Product Structure:
-
Controller: 4kg
-
Primary Booster (40kV): 25kg
-
Two-stage Booster (40/50kV): 45kg
-
-
Application Range: Used for voltage resistance test of cables and motors greater than 35KV
VLF30/40kV / VLF50kV/VLF60kV/VLF80/90kV
Key Features:
-
Data of current and voltage are obtained directly through the sampling of the high-pressure side.
-
Over-voltage protection: shut down protection operates within 20ms when the output voltage exceeds limits.
-
Over-current protection: dual protection of high and low voltage, downtime protection can be accurately set on the high-pressure side, and shut down protection operates within 20ms when the current of the low-voltage side exceeds current limits.
-
High-voltage output protection resistor is integrated into the HV booster, eliminating the need for an additional outside resistor.
-
The settings allow you to regulate the frequency, which can be adjusted to the following output frequencies: 0.1, 0.05, and 0.02Hz.
-
Closed-loop negative feedback control circuit of high and low voltage.
-
Measurement accuracy: 3%.
-
Positive and negative voltage peak errors: ≤ 3%.
-
Voltage waveform distortion: ≤ 5%.
-
Operating Temperature (indoor and outdoor): -10℃ to +40℃.
-
Humidity: ≤ 85% RH.
-
Power: AC 50Hz, 220V ±5%.