MTS-100 Meter Test System
About the MTS-100:
-
Phase: 3
AC voltage output: 0-792V
AC current output: 0-120A
Accuracy: 0.05%RG (Class 0.05) or 0.1% RG (Class 0.1)
-
This Meter Test System features state-of-art designing with high accuracy. It is composed of high accurate (class 0.05% or 0.1%) standard reference meter and power source (up to 120A). This system is particularly designed with modular structure for calibration and test of different single phase/3 phase electronic/inductive active and reactive energy meters.
Order Info:
MTS-100 contains 2 models with different accuracy below:
-
MTS-100C: Accuracy Class 0.05
-
MTS-100B: Accuracy Class 0.1
Specifications:
AC Voltage output:
-
Range: 100V, 220V, 380V
-
Adjusting Range: (0~120)% RG (RG refers to range)
-
Adjusting Resolution: 0.01% RG, 0.1% RG, 1% RG, or 10% RG
-
Stability: 0.01%/2min (Class 0.05), 0.02%/2min (Class 0.1)
-
Distortion: ≤0.2% (Non-capacitive load)
-
Max Output Load: 20VA each phase
-
Accuracy: 0.05% RG (Class 0.05), 0.1% RG (Class 0.1)
AC Current output:
-
Range: 0.05A, 0.2A, 1A, 5A, 20A, 100A
-
Adjusting Range: (0~120)% RG
-
Adjusting Resolution: 0.01% RG, 0.1% RG, 1% RG, or 10% RG
-
Stability: 0.01%/2min (Class 0.05), 0.02%/2min (Class 0.1)
-
Distortion: ≤0.2% (Non-capacitive load)
-
Max Output Load: 120VA (100A range)
-
Accuracy: 0.05% RG (Class 0.05); 0.1% RG (Class 0.1)
Power output:
-
Power Output Stability: 0.01%/2min (Class 0.05), 0.02%/2min (Class 0.1)
-
Active/Reactive Power Measurement Accuracy: 0.05% RG
Phase output:
-
Output Adjusting Range: 0°~360°
-
Output Adjusting Resolution: 10°, 1°, 0.1°, or 0.01°
-
Resolution: 0.01°
-
Measurement Accuracy: 0.05°
Power factor output:
-
Adjusting Range: -1 ~ 0 ~ +1
-
Measuring Resolution: 0.0001
-
Measurement Accuracy: 0.0005
Frequency output:
-
Adjusting Range: 40Hz ~ 70Hz
-
Output Adjusting Resolution: 1Hz, 0.1Hz, 0.01Hz, or 0.001Hz
-
Resolution: 0.001Hz
-
Accuracy: 0.002Hz
Harmonic setting:
-
Harmonic Order: 2nd ~ 63rd
-
Harmonic Amplitude: 0~40%
-
Harmonic Angle: 0°~359.99°
-
Harmonic Set Error:
-
2nd ~ 31st: ≤±0.1%
-
32nd ~ 63rd: ≤±0.2%
-
Energy error measurement:
-
Active Energy Basic Error Limit:
-
±0.05% RD (Voltage 15V660V, Current 0.02A120A, PF ≥0.5)
-
±0.1% RD (Voltage 15V660V, Current 0.01A0.02A, PF =1)
-
-
Reactive Energy Basic Error Limit:
-
±0.1% RD (Voltage 15V660V, Current 0.02A120A, PF ≥0.5)
-
±0.2% RD (Voltage 15V660V, Current 0.01A0.02A, PF =1)
-
Energy pulse input:
-
Input Pulse: 3 channels active, 3 channels reactive
Other parameters:
-
Power Supply: 90-265VAC/DC
-
Power Frequency: 50Hz~60Hz
-
Power Consumption: 50VA~1000VA
-
Environment Condition: 20℃~30℃, Humidity: RH ≤85%
-
Storage Environment: -20℃~50℃
-
Size: 600mm (L) × 440mm (W) × 266mm (H)
-
Weight: 35kg
-
Calibrate all kind of single/three phase electronic/inductive active and reactive energy meter
-
Automatically or single-step manually test basic error, creeping, starting, standard deviation of single/three phase energy meter, save user-defined calibrating scheme in Auto calibration
-
Support variables influencetests, such as: Voltage, frequency, harmonics, reverse phase sequence, Voltage unbalance, etc
-
Support special tests in energy meter type test, such as: phase triggering, pulse train triggering, etc
-
Support DLT-645 communication protocol,multi-testing of multifunction meter such as: demand indication error, demand cycle error, time slot switching error, energy error of different tariff period, etc
-
With OCXO, daily error of energy meter can be detected
-
Output 2nd~63rd
-
8” TFT screen, interface friendly, easy to operate;
-
Equipped with RS232, Ethernet, and WiFi interface,MTS-100 can either support stand-alone operation, PC control or handy wireless terminal control;
-
Communicate with tested meters thru RS-485;
-
Automatically calculate the error of meter, and the related data can be downloaded thru U-disk;
-
Self-protection, alarming and displaying overload location for equipment output overload, Voltage short-circuit, Current open-circuit;
-
Automatically detect, diagnose and alarm for failure.
-
Remotely updating online, easily achieve software updating;
-
Support calibration by user locally.