Introduction to the TM25t:
  • Testing of the power transmission towers grounding (G) quality poses a serious problem as they are all electrically interconnected by means of Ground Wires which act as lightning rods, protecting the lines from atmospheric discharges. Due to the existence of this connection, any attempt to measure a tower grounding (G) resistance using a conventional earth meter leads to wrong results as what is really being measured is all the shunt towers grounding (G) resistance (or, more precisely, its impedance at low frequency).
     

  • To make this kind of test feasible, which is of vital importance to ensure the transmission of the electrical power without interruptions, TENTECH TM25t grounding resistance meter for high frequency has been developed. This is the appropriate tool for a fast, safe and reliable grounding resistance measurement in each tower of a working line transmission, without disconnecting the ground wire.
     

  • Its operation is based on the use of a high-frequency measurement current (25 kHz), for which ground wire inductive impedance - taking into account a typical length span - is reasonably high, making it possible to reduce the effect of the adjacent towers under measurement. The equipment only measures the ground resistance of the surveyed tower, including its base. The extensive G systems, such as meshes, buried wires, metal pipes, etc, are measured only considering the closest section to the connection point, so that the measured value represents the performance against a pulse signal similar to an atmospheric discharge. Thus, values that better represent the system capacity to ground lightning currents than the ones obtained with low frequency conventional equipments, even when disconnecting the ground wire, are obtained. TM25t is a strong equipment, easy to carry, resistant to the hard weather and geographical features of the tropical and high-mountain regions, that is why it is described as an excellent product for field works under the most severe environmental conditions.

The TM25t
Technical Specifications

Measurement Ranges

  • 0 - 300 Ω

Operation Frequency

  • 25,000 Hz

Test Current

  • 20 mA automatic

Inductive Component Compensation

  • Through bank of capacitors integrated into the equipment

  • Maximum capacity: 4.2 μF

  • Resolution: 10 nF

Measurement Accuracy

  • ± 2.5 % of reading ± 1 digit

Max. Earth Resistance of Auxiliary Rods

  • Current rod: 2,000 Ω

  • Voltage rod: 2,000 Ω

Display

  • Alphanumerical LCD display, 4 lines / 20 characters (Big Number)

Printer

  • Built-in thermal printer

Built-in Memory

  • Stores up to 2,000 test readings in internal NVRAM memory

Protocol

  • Modbus

USB

  • For configuration, control, and downloading stored values

Bluetooth

  • For configuration, control, and downloading stored values

Overvoltage Protection

  • CAT IV - 300 V

Safety

  • IEC 61010-1

Desktop Software (PC/Notebook)

  • TLogger software: Allows remote control, configuration, test execution, and report generation

Android App (Smartphone/Tablet)

  • TENTECH Remote Control app: Allows remote control, configuration, test execution, and report generation

IP Rating

  • IP65 (with closed lid)

Operating Temperature

  • 14 °F to 122 °F (-10 °C to 50 °C)

Storage Temperature

  • -13 °F to 158 °F (-25 °C to 70 °C)

Humidity

  • 95 % RH (non-condensing)

Power Supply

  • Internal rechargeable battery (LFP 12 V 6000 mA)

Battery Charger

  • 12 V - 2 A

Equipment Weight

  • Approx. 10.80 lb (4.9 kg)

Dimensions

  • 13.6" x 10.7" x 6.3" (345 x 272 x 159 mm)

Features
  • Intended for measurement of earth resistance of electricity pylons

  • Minimizes the influence of adjacent pylons, connected by the guard cable

  • Operation frequency: 25 kHz

  • Resistance reading: up to 300 Ω

  • Automatic current injection

  • Built-in memory and printer

  • Rechargeable battery

Included accessories
  • 8x 19.6" (50 cm) long steel core rods with copper coating

  • 6x 6.5 ft (2 m) cables for interconnection of extra auxiliary rods

  • Rod extractor

  • 229.6 ft (70 m) shielded cable

  • 164 ft (50 m) shielded cable

  • 98.4 ft (30 m) cable to current rod

  • 229.6 ft (70 m) cable to auxiliary potential rod

  • 164 ft (50 m) cable to auxiliary potential rod

  • Cable adapter for current electrode

  • AC Adapter

  • Cable for connection to the unknown electrode (Tower)

  • USB cable

  • User guide

  • TLogger software (download)

  • TENTECH Remote Control app (download)

  • Case to carry accessories

Email:  info@itesouthafrica.com 

Address:  Unit B1,Sanlam Industrial Park,

 

      Masjien Street,Strydom Park,

Randburg, Gauteng

 

South Africa

Phone:  +27 (0)872658722

© 2021 ITESA - Industrial Test Equipment South Africa  |  Terms and Conditions  |  Privacy Policy

bottom of page