CBA.307A
About the CBA.307A:
-
Circuit Breaker Analyzer CBA.307 is used for testing, analysing and assessing power system circuit breakers, mechanical characteristics of load switches and isolated switches and other AC high voltage switches, contact resistance, arcing contacts and vibration characteristics etc.
-
The functions of Circuit Breaker Analyzer cover all testing items of high voltage circuit breaks.
-
Comparing with the traditional circuit breaker tester, this analyser has unique advantages.
Test Specifications:
Channels for Time Measurement
12 channels (3 channels support both time contact and resistance contact time)
6 isolated channels for cascaded unit measurement of the pole
Analogue Input Channels
4 channels:
-
1 for travel sensor
-
3 for vibration sensors (can also be used for other analogue sensors)
Time Measurement
-
Range: 4000ms
-
Error: < 0.1ms
-
Resolution: 0.01ms
Travel Measurement (according to sensor)
-
Linear Resistance Sensor:
-
Measurement Range: 0~250mm
-
Resolution: 0.01mm
-
Error: < 0.5mm
-
-
Measurement Range: 0~25mm
-
Resolution: 0.01mm
-
Error: < 0.05mm
-
-
Angle Resistance Sensor:
-
Measurement Range: 0~360°
-
Resolution: 0.01°
-
Error: < 0.5°
-
-
Pre-Insertion Resistance Measurement
-
Range: 50~5000ohm
-
Error: < 1% RDG + 2D
Dynamic Resistance Measurement
-
Test Current: 25~100A
-
Measurement Error: < 1% RDG + 2D
External Trigger Voltage
-
AC/DC: 10-300V
-
Current: ≤120A
Contact Resistance Measurement
-
Range: 0~10mohm
-
Error: < 0.5% RDG + 0.05% FS
-
Range: 0~2mohm
-
Error: < 0.5% RDG + 2D
Speed Measurement
-
250mm Linear Resistance Scale:
-
Range: 0~20m/s
-
Error: < 0.5% RDG + 2D
-
-
25mm Linear Resistance Scale:
-
Range: 0~20m/s
-
Error: < 0.5% RDG + 2D
-
-
Angle Sensor:
-
Range: 0~20m/s
-
Error: < 0.5% RDG + 2D
-
-
Acceleration Sensor:
-
Range: 0~20m/s
-
Error: < 5% RDG + 2D
-
Coil Current Measurement
-
Range: 0~20A
-
Resolution: 0.001A
-
Error: < 0.01A
Vibration Measurement
-
Range: 0~5000G
-
Error: < 3%
Internal DC Power Source
-
Voltage: 24~265V
-
Current: 0~20A
Storage & Data Export
-
Built-in Memory: 8GB
-
USB Interfaces: 2 for data export and external keyboard or mouse connection
Software Compatibility
-
OS: Windows 7, 8 & 10 (32-bit minimum required)
Power Supply
-
AC Input: 220V ±10%, 50Hz ±10%
Working Environment
-
Temperature: -10~50°C
-
Humidity: < 80%
Dimensions & Weight
-
Dimensions: 448mm × 260mm × 150mm
-
Weight: 15kg
Features:
-
Measurement of closing time, opening time, time spread between poles, time spread between units of one pole, bounces.
-
Measurement of closing, opening speed and average speed.
-
Measurement of clearance between open contacts, over travel, overshoot travel and total travel.
-
Measurement of closing coil current time curve, opening coil current time curve and the maximum coil current.
-
Test travel time curve, speed time and acceleration time curve.
-
Test contact dynamic resistance, time curve and Length.
-
CO-t1-CO, O-t-CO-t1-CO, CO rated operating verification test.
-
Mechanical travel automatic compare with saved travel curve.
-
Measurement of CO time (close-open time) and OC time (Opening-Closing time).
-
Graphite contact closing time, opening time, dynamic resistance curve measurement.
-
Zoom, editors, statistics and analysis for measurement curves.
-
2.1-inch touch screen for control and data input.
-
Built-in micro printer for on-site test result printout.
-
Generate WORD format test report automatically (all reports and data can be exported via Flash disk).
Software: